Function
Description
2.3. dTMin tank1
Difference (ΔT) between collector temperature (T1) and Tank1 temperature
(T2) that will automatically disengage pump1. Set to 4
°
F
2.10. Mintemp Collector
Select the minimum collector temperature required for system start-up. Set to
85
°
F
2.11.1. Thermostat Start
When the water temp. at the location of T3 drop below this setting P3 will start.
Set to 125
°
F
2.11.2. Hysteresis
When the water temp. at the location of T3 exceeds the Start temperature plus
the Hysteresis setting, P3 will shutoff. Set to 30
°
F
7.12. Replace Front Case
Push the front case into place while making sure to feed the pump power cable through the hole into the
controller enclosure. The casing will simply lock into place.
8. Direct Flow Pump Station Installation
󱚡 NOTICE
The following instructions are specific to the Apricus Direct Flow Pump Station, which is
designed for use in Apricus OG-300 certified open loop systems.
8.1. Design
a) The Apricus Direct Flow Pump Station (ADFPS) is specifically designed for use with the Apricus solar
collector in a direct flow format. It is NOT suitable for closed loop or drain-back systems.
b) The ADFPS has the following key features:
Single Speed Stainless Steel Grundfos pump (with integrated check valve)
Controller mounted directly into pump station 3/4” Quick connector push fittings
75 psi pressure relief valve Flow meter with built in balancing valve
Power outage drain valve for freeze protection even without power.
8.2. Direct Flow Pump Station Technical Data
Pump Station
Direct Flow
Overall Depth
8.375” / 213 mm (With Insulated Cover)
Overall Height
24.5” / 622 mm
Overall Width
17.5” / 444 mm
Weight (Empty)
24 lb. /10.9 kg.
Solar Connection
¾” (7/8” OD copper) Quick Connect Fitting
Tank Connection
¾” (7/8” OD copper) Quick Connect Fitting
Pressure Relief Valve Connection
¾” FPT
Pressure Relief Valve Pressure
75psi / 5.1bar
Apricus Solar Collector Installation & Operation Manual - USA
Copyright © 2011 – Apricus Inc Doc: A7-05.4.12-PB Page 63 of 129